OSHA 10 General Industry Practice Test

Practice for the OSHA 10-hour general industry course, the one plant, shop and building maintenance workers take, and the test a trainer may give at its end. Pick an answer to see whether it is right and the OSHA standard behind it.

38
practice questions
each with its answer explained
8
sections
Introduction to OSHA and workers' rights, Walking-working surfaces and fall protection, Exit routes, emergency action and fire protection, Electrical, Personal protective equipment, Hazard communication, Lockout/tagout (elective), Machine guarding (elective)

What the real course is like

Plants, warehouses and facilities often ask maintenance technicians, plant electricians and building engineers for an OSHA 10 General Industry card.

  • The OSHA Outreach Training Program is voluntary: the 10-hour general industry class does not meet the training requirements of any OSHA standard and the federal government does not require it, but some states and local jurisdictions have made Outreach training mandatory. (OSHA Outreach Training Program, General Industry Procedures (2024), Section II, General Industry Overview)
  • The 10-hour general industry class runs at least 10 hours: 6 required hours of 1 hour each (Introduction to OSHA; walking and working surfaces, including fall protection; exit routes, emergency action plans, fire prevention plans and fire protection; electrical; personal protective equipment; hazard communication), at least 2 elective hours and 2 optional hours. (OSHA Outreach Training Program, General Industry Procedures (2024), Section IV.A)
  • The elective hours cover at least two topics of at least 30 minutes each, chosen from hazardous materials, permit-required confined spaces, lockout/tagout, machine guarding, welding, cutting and brazing, industrial hygiene, bloodborne pathogens, ergonomics, fall protection, safety and health programs, powered industrial vehicles and materials handling. (OSHA Outreach Training Program, General Industry Procedures (2024), Section IV.A.2)
  • Training is limited to 7.5 student contact hours per calendar day, so a 10-hour class takes at least two calendar days, and a student must attend the entire class to receive the card. (OSHA Outreach Training Program Requirements (2024), Section V.F, Training Delivery)
  • OSHA does not require a test to earn the card: a trainer may give one to check learning, test time does not count toward the 10 hours, and general industry course completion cards have no expiration date. (OSHA Outreach Training Program Frequently Asked Questions)
  • OSHA lists the authorized online providers of the 10-hour general industry class on osha.gov and says it cannot validate training offered by vendors not on that list. (OSHA-Authorized Online Outreach Training Providers)

The practice test

Pick an answer to see whether it is right. Each explanation shows why, with the rule or the working behind it, so a wrong answer still teaches you something.

0 of 38 answered

Introduction to OSHA and workers' rights (5) · Walking-working surfaces and fall protection (5) · Exit routes, emergency action and fire protection (5) · Electrical (5) · Personal protective equipment (5) · Hazard communication (5) · Lockout/tagout (elective) (4) · Machine guarding (elective) (4)

Introduction to OSHA and workers' rights

Inspections, citations, access to injury and exposure records, and protection from retaliation.

  1. 1. An OSHA compliance officer arrives to inspect a plant. Who must be given the chance to go along on the walkaround of the workplace?

    Show the answer

    B. A representative of the employer and a representative authorized by the employees. 29 CFR 1903.8(a) puts the compliance officer in charge of the inspection and requires that a representative of the employer and a representative authorized by the employees be given an opportunity to accompany the officer during the physical inspection, to aid the inspection.

    From 29 CFR 1903.8(a)

  2. 2. OSHA cites a plant for an unguarded machine. How long must the citation stay posted at or near the place where the violation occurred?

    Show the answer

    A. Until the violation is corrected or for 3 working days, whichever is later. 29 CFR 1903.16(a) requires the employer to post the citation, unedited, at or near each place an alleged violation occurred as soon as it is received. Under 1903.16(b) it stays posted until the violation is abated or for 3 working days, whichever is later, and contesting the citation does not end that duty.

    From 29 CFR 1903.16(a) and (b)

  3. 3. A machine operator asks for a copy of the OSHA 300 Log for the plant where she works. By when must the employer give it to her?

    Show the answer

    C. By the end of the next business day. Under 29 CFR 1904.35(b)(2)(iii), when an employee, former employee, personal representative or authorized employee representative asks for the OSHA 300 Log, the employer must provide a copy by the end of the next business day. Under 1904.35(b)(2)(vi) the first copy is free.

    From 29 CFR 1904.35(b)(2)(iii)

  4. 4. A worker asks to see the employer's records of his own exposure to solvents. Under 29 CFR 1910.1020, if the employer cannot give access within how many working days must it, within that time, tell him the reason for the delay and the earliest date the records will be available?

    Show the answer

    D. 15 working days. 29 CFR 1910.1020(e)(1)(i) requires access to a requested record in a reasonable time, place and manner. If the employer cannot provide it within 15 working days, it must tell the employee or designated representative, within those 15 working days, why and when the record will be available.

    From 29 CFR 1910.1020(e)(1)(i)

  5. 5. A worker is demoted after reporting a hazard and files a retaliation complaint with OSHA under Section 11(c) of the OSH Act. Within how many days of receiving the complaint does the Act direct OSHA to notify the worker of its determination?

    Show the answer

    C. 90 days. Section 11(c)(1) bars any person from discharging or discriminating against an employee for filing a complaint or using a right under the Act, and 11(c)(2) gives the employee 30 days after the violation to file. Section 11(c)(3) directs the Secretary of Labor (OSHA) to notify the complainant of the determination within 90 days of receiving the complaint.

    From OSH Act of 1970, Section 11(c) (29 USC 660(c))

Walking-working surfaces and fall protection

When fall protection is required, fixed and portable ladders, and stair handrails (29 CFR 1910 Subpart D).

  1. 6. A maintenance technician services a fan on a mezzanine with an open, unprotected edge. Under OSHA's general industry rule, at what height above the lower level must the employer protect the technician from falling?

    Show the answer

    A. 4 feet or more. 29 CFR 1910.28(b)(1)(i) requires each employee on a walking-working surface with an unprotected side or edge 4 feet or more above a lower level to be protected by a guardrail system, a safety net system or a personal fall protection system (personal fall arrest, travel restraint or positioning).

    From 29 CFR 1910.28(b)(1)(i)

  2. 7. A fixed ladder installed at a plant in 2025 climbs 30 feet to a roof. What must it be equipped with?

    Show the answer

    D. A personal fall arrest system or a ladder safety system. 29 CFR 1910.28(b)(9)(i)(B) requires every fixed ladder that extends more than 24 feet above a lower level and was installed on or after November 19, 2018 to have a personal fall arrest system or a ladder safety system. A cage or well counts only on ladders installed before that date, and by November 18, 2036 every such fixed ladder must have one of the two systems (1910.28(b)(9)(i)(A) and (D)).

    From 29 CFR 1910.28(b)(9)(i)

  3. 8. During the check before the shift, a worker finds a cracked side rail on an extension ladder. What must happen to the ladder?

    Show the answer

    C. It must be tagged "Dangerous: Do Not Use" (or similar) and removed from service until it is repaired or replaced. 29 CFR 1910.23(b)(9) requires ladders to be inspected before initial use in each work shift. Under 1910.23(b)(10), any ladder with structural or other defects is immediately tagged "Dangerous: Do Not Use" or with similar language and removed from service until repaired or replaced.

    From 29 CFR 1910.23(b)(9) and (b)(10)

  4. 9. A worker on a stepladder needs a little more reach. Which rule in 29 CFR 1910.23 applies?

    Show the answer

    B. The cap and the top step of a stepladder may not be used as steps. 29 CFR 1910.23(c)(8) requires that the cap (if the ladder has one) and the top step of a stepladder not be used as steps. The worker needs a taller ladder. Under 1910.23(c)(2), a stepladder must also have a metal spreader or locking device holding it open while in use.

    From 29 CFR 1910.23(c)(8)

  5. 10. A new handrail is being installed on a stairway in a plant. Measured from the leading edge of the stair tread to the top of the handrail, how high must it be?

    Show the answer

    C. Between 30 and 38 inches. 29 CFR 1910.29(f)(1)(i) requires handrails to be not less than 30 inches and not more than 38 inches high, measured from the leading edge of the stair tread to the top surface of the handrail. The 42-inch minimum in 1910.29(f)(1)(ii)(B) is for stair rail systems installed on or after January 17, 2017, not for handrails.

    From 29 CFR 1910.29(f)(1)

Exit routes, emergency action and fire protection

Exit doors and widths, emergency action plans and portable fire extinguishers (29 CFR 1910.36 to 1910.39 and 1910.157).

  1. 11. To stop theft, a manager wants to padlock a side exit door from the inside while the night shift is working. What does 29 CFR 1910.36(d) require?

    Show the answer

    D. Employees must be able to open an exit route door from the inside at all times without keys, tools or special knowledge. 29 CFR 1910.36(d)(1) requires that employees be able to open an exit route door from the inside at all times without keys, tools or special knowledge. A device such as a panic bar that locks only from the outside is permitted on exit discharge doors.

    From 29 CFR 1910.36(d)(1)

  2. 12. What is the minimum width of an exit access at all points, including where carts or racks stand along it?

    Show the answer

    B. 28 inches. 29 CFR 1910.36(g)(2) requires an exit access to be at least 28 inches wide at all points, and 1910.36(g)(4) bars objects that project into the exit route from reducing it below that minimum. Under 1910.36(g)(1), the ceiling of an exit route must be at least 7 feet 6 inches high.

    From 29 CFR 1910.36(g)

  3. 13. A machine shop with 8 employees must have an emergency action plan under an OSHA standard. What does 29 CFR 1910.38 allow?

    Show the answer

    A. The plan may be communicated orally to employees. 29 CFR 1910.38(b) requires an emergency action plan to be in writing, kept in the workplace and available to employees for review, but an employer with 10 or fewer employees may communicate the plan orally. 1910.38(c) lists what the plan must cover, such as reporting emergencies, evacuation and accounting for all employees.

    From 29 CFR 1910.38(b)

  4. 14. Portable fire extinguishers are provided for employees to use on Class A fires (ordinary combustibles such as wood, paper and cardboard). What is the greatest travel distance allowed from an employee to an extinguisher?

    Show the answer

    C. 75 feet. 29 CFR 1910.157(d)(2) requires extinguishers for Class A fires to be distributed so the travel distance for employees to any extinguisher is 75 feet or less. For Class B hazards (flammable liquids), 1910.157(d)(4) sets 50 feet or less from the hazard area.

    From 29 CFR 1910.157(d)(2) and (d)(4)

  5. 15. How often must the employer have portable fire extinguishers visually inspected, and how often must they get a maintenance check?

    Show the answer

    D. Inspected monthly, and a maintenance check every year. 29 CFR 1910.157(e)(2) requires portable extinguishers to be visually inspected monthly, and 1910.157(e)(3) requires an annual maintenance check, with the date recorded and the record kept for one year after the last entry or the life of the shell, whichever is less.

    From 29 CFR 1910.157(e)(2) and (e)(3)

Electrical

Working space at panels, flexible cords, tripped breakers, overhead lines and GFCIs (29 CFR 1910 Subpart S).

  1. 16. A 120/240-volt panelboard (120 volts to ground) was installed in a plant in 2020 and may be serviced while energized. What is the minimum depth of clear working space in front of it?

    Show the answer

    C. 3 feet. 29 CFR 1910.303(g)(1)(i)(A) and Table S-1 set a minimum depth of 3 feet for 0 to 150 volts to ground under every condition (2.5 feet is allowed only for installations built before April 16, 1981). The space must also be at least 30 inches wide or the width of the equipment, whichever is greater, and 1910.303(g)(1)(ii) bars using it for storage.

    From 29 CFR 1910.303(g)(1) and Table S-1

  2. 17. A technician wants to power a machine in the next room permanently by running an extension cord through a hole in the wall. What does 29 CFR 1910.305(g)(1)(iv) say?

    Show the answer

    D. It is not allowed: a flexible cord may not substitute for fixed wiring or be run through holes in walls, ceilings or floors. 29 CFR 1910.305(g)(1)(iv) bars flexible cords from being used as a substitute for the fixed wiring of a structure, run through holes in walls, ceilings or floors, run through doorways or windows, attached to building surfaces or concealed behind walls, ceilings or floors.

    From 29 CFR 1910.305(g)(1)(iv)

  3. 18. The circuit breaker feeding a conveyor motor trips. What does 29 CFR 1910.334(b)(2) require before the circuit is turned back on?

    Show the answer

    A. It may not be manually reenergized until it has been determined that the equipment and circuit can be safely energized. 29 CFR 1910.334(b)(2) bars manually reenergizing a circuit deenergized by a protective device until it is determined that the equipment and circuit can be safely energized, and it prohibits repetitive manual reclosing of breakers. 1910.334(b)(3) bars modifying overcurrent protection, even temporarily.

    From 29 CFR 1910.334(b)(2) and (b)(3)

  4. 19. An unqualified maintenance worker is cleaning gutters on a roof near an unguarded overhead line energized at 70 kV to ground. How close may the worker, and the longest conductive object he could contact, come to the line?

    Show the answer

    C. 10 feet 8 inches. 29 CFR 1910.333(c)(3)(i)(A) sets 10 feet for lines up to 50 kV to ground, plus 4 inches for every 10 kV over 50 kV. The line is 20 kV over 50 kV, which is two steps of 4 inches, so 10 feet plus 8 inches is 10 feet 8 inches.

    From 29 CFR 1910.333(c)(3)(i)(A)

  5. 20. Under 29 CFR 1910.304(b)(3)(i), which receptacles in a workplace must have ground-fault circuit-interrupter (GFCI) protection for personnel?

    Show the answer

    B. All 125-volt, single-phase, 15- and 20-ampere receptacles installed in bathrooms or on rooftops. 29 CFR 1910.304(b)(3)(i) requires GFCI protection for personnel on all 125-volt, single-phase, 15- and 20-ampere receptacles installed in bathrooms or on rooftops. Temporary wiring used during maintenance, remodeling or repair has its own GFCI rule in 1910.304(b)(3)(ii).

    From 29 CFR 1910.304(b)(3)(i)

Personal protective equipment

Hazard assessment, eye protection, insulating gloves, respirator fit testing and hearing protection (29 CFR 1910 Subpart I and 1910.95).

  1. 21. An employer has assessed a shop for hazards that call for PPE. How must it show the hazard assessment was done?

    Show the answer

    D. A written certification naming the workplace evaluated, the person certifying the evaluation and the date(s) of the assessment, identified as a certification of hazard assessment. 29 CFR 1910.132(d)(1) requires the employer to assess the workplace for hazards that call for PPE, select PPE that protects against them and fits each worker, and tell each affected worker. Under 1910.132(d)(2), the assessment is verified by a written certification that identifies the workplace evaluated, the person certifying, the date(s) and the document as a certification of hazard assessment.

    From 29 CFR 1910.132(d)

  2. 22. A machinist who wears prescription glasses runs a lathe that throws chips. What eye protection meets 29 CFR 1910.133(a)(3)?

    Show the answer

    A. Safety eyewear that has the prescription built in, or eye protection worn over the glasses without disturbing them. 29 CFR 1910.133(a)(3) requires a worker who wears prescription lenses around eye hazards to wear eye protection that incorporates the prescription, or eye protection that can be worn over the prescription lenses without disturbing the position of either lens. Under 1910.133(a)(2), protection from flying objects must also give side protection.

    From 29 CFR 1910.133(a)(2) and (a)(3)

  3. 23. A plant electrician is issued rubber insulating gloves. At a minimum, how often must the gloves be electrically tested?

    Show the answer

    B. Before first issue and every 6 months after that. Table I-5 of 29 CFR 1910.137 requires rubber insulating gloves to be tested before first issue and every 6 months after, and also when their insulating value is suspect, after repair and after use without protectors (blankets and sleeves are every 12 months). Under 1910.137(c)(2)(ii), gloves are also inspected and air tested before each day's use.

    From 29 CFR 1910.137(c)(2) and Table I-5

  4. 24. A maintenance technician wears a tight-fitting half-mask respirator. When must he be fit tested?

    Show the answer

    C. Before first use, whenever a different facepiece size, style, model or make is used, and at least annually. 29 CFR 1910.134(f)(2) requires fit testing before initial use of a tight-fitting respirator, whenever a different facepiece (size, style, model or make) is used, and at least annually after that. Under 1910.134(e)(1), the medical evaluation comes before the fit test.

    From 29 CFR 1910.134(f)(2)

  5. 25. At what 8-hour time-weighted average noise level must an employer make hearing protectors available to employees at no cost?

    Show the answer

    D. 85 decibels. 29 CFR 1910.95(i)(1) requires hearing protectors to be available, at no cost, to all employees exposed to an 8-hour TWA of 85 decibels or more. The same 85-decibel action level triggers the hearing conservation program under 1910.95(c)(1), including annual audiograms under 1910.95(g)(6).

    From 29 CFR 1910.95(i)(1)

Hazard communication

Container labels, safety data sheets and the written program (29 CFR 1910.1200).

  1. 26. A worker pours a solvent from a labeled drum into a small can that only he will use right away. Under the Hazard Communication Standard, what label does the can need?

    Show the answer

    C. None, because it is a portable container intended only for the immediate use of the employee who made the transfer. 29 CFR 1910.1200(f)(8) exempts from labeling a portable container that holds a hazardous chemical transferred from a labeled container and is intended only for the immediate use of the employee who made the transfer. Any other workplace container needs a label under 1910.1200(f)(6).

    From 29 CFR 1910.1200(f)(8)

  2. 27. A worker gets a chemical splashed in the eye. Which section of the product's safety data sheet (SDS) gives the first-aid measures?

    Show the answer

    B. Section 4. 29 CFR 1910.1200(g)(2) sets the 16 SDS sections in a fixed order: Section 4 is First-aid measures. Section 2 is Hazard(s) identification, Section 7 is Handling and storage and Section 11 is Toxicological information.

    From 29 CFR 1910.1200(g)(2)

  3. 28. Where and when must safety data sheets be available to workers?

    Show the answer

    B. Readily accessible to workers in their work areas during each work shift, on paper or electronically if nothing blocks immediate access. 29 CFR 1910.1200(g)(8) requires the employer to keep an SDS for each hazardous chemical in the workplace, readily accessible during each work shift to employees in their work areas. Electronic access is allowed as long as it creates no barrier to immediate employee access.

    From 29 CFR 1910.1200(g)(8)

  4. 29. A cleaner is transferred into a spray bottle that will stay on a shelf for several workers to use. Other than the full shipped-container label, what label does 29 CFR 1910.1200(f)(6) allow on the bottle?

    Show the answer

    A. The product identifier, plus words, pictures or symbols that give at least general information about its hazards. 29 CFR 1910.1200(f)(6) requires each workplace container to carry either the full shipped-container label information or the product identifier with words, pictures or symbols giving at least general hazard information, which together with the rest of the program gives the specific hazards. Under 1910.1200(f)(10), workplace labels must be legible, in English and prominently displayed.

    From 29 CFR 1910.1200(f)(6) and (f)(10)

  5. 30. Besides describing how labels, safety data sheets and training will be handled, what must an employer's written hazard communication program include?

    Show the answer

    D. A list of the hazardous chemicals known to be present, using product identifiers that match their safety data sheets. 29 CFR 1910.1200(e)(1) requires a written program at each workplace that includes a list of the hazardous chemicals known to be present, by a product identifier referenced on the SDS, and the methods for informing employees of the hazards of non-routine tasks and of chemicals in unlabeled pipes in their work areas.

    From 29 CFR 1910.1200(e)(1)

Lockout/tagout (elective)

Controlling hazardous energy: the procedure, removing locks, verification and the cord-and-plug exception (29 CFR 1910.147).

  1. 31. How often must the employer inspect each energy control (lockout/tagout) procedure, and who does the inspection?

    Show the answer

    B. At least annually, by an authorized employee other than the one(s) using the procedure being inspected. 29 CFR 1910.147(c)(6)(i) requires a periodic inspection of the energy control procedure at least annually. It must be done by an authorized employee other than the one(s) using the procedure being inspected, and any deviations or inadequacies found must be corrected.

    From 29 CFR 1910.147(c)(6)(i)

  2. 32. A mechanic who locked out a press has gone home with his key, and the press is needed on the next shift. Under 29 CFR 1910.147(e)(3), how may his lock be removed?

    Show the answer

    A. Under the employer's direction, by a documented procedure the employees are trained in: verify he is not at the facility, make all reasonable efforts to contact him, and make sure he knows before he resumes work. 29 CFR 1910.147(e)(3) requires each lock or tag to be removed by the employee who applied it. The only exception is removal under the employer's direction through a specific, documented procedure with training that verifies the employee is not at the facility, makes all reasonable efforts to contact him, and ensures he knows before he resumes work there.

    From 29 CFR 1910.147(e)(3)

  3. 33. An authorized employee has shut down a mixer, operated its disconnect, applied a lock and relieved the stored energy. What must happen before work starts?

    Show the answer

    B. The authorized employee must verify that the mixer has actually been isolated and deenergized. 29 CFR 1910.147(d) sets the sequence: preparation, shutdown, isolation, applying the lockout or tagout devices, relieving stored energy, and then, under 1910.147(d)(6), verifying before work starts that isolation and deenergization have been accomplished.

    From 29 CFR 1910.147(d)(6)

  4. 34. A technician will replace the belt on a cord-and-plug connected bench sander. When does the lockout/tagout standard not apply to this work?

    Show the answer

    A. When the sander is unplugged and the plug stays under the exclusive control of the technician doing the work. 29 CFR 1910.147(a)(2)(iii)(A) excludes work on cord-and-plug connected electric equipment when the hazard of unexpected startup is controlled by unplugging the equipment and keeping the plug under the exclusive control of the employee doing the servicing or maintenance.

    From 29 CFR 1910.147(a)(2)(iii)(A)

Machine guarding (elective)

Point of operation guarding, fan guards and bench grinder adjustments (29 CFR 1910.212 and 1910.215).

  1. 35. A machine operator uses tongs to feed small parts into a forming machine. What does 29 CFR 1910.212(a)(3)(iii) say about such hand tools?

    Show the answer

    D. They may supplement the required guarding but may not take its place. The point of operation is where work is actually performed on the material, and under 29 CFR 1910.212(a)(3)(ii) it must be guarded so no part of the operator's body is in the danger zone during the operating cycle. Under 1910.212(a)(3)(iii), special hand tools for placing and removing material may only supplement that guarding, never replace it.

    From 29 CFR 1910.212(a)(3)

  2. 36. A pedestal fan in a shop has blades whose outer edge is 5 feet above the floor. What does 29 CFR 1910.212(a)(5) require?

    Show the answer

    B. A guard with openings no larger than 1/2 inch. 29 CFR 1910.212(a)(5) requires fan blades to be guarded when their periphery is less than 7 feet above the floor or working level, with guard openings no larger than 1/2 inch.

    From 29 CFR 1910.212(a)(5)

  3. 37. On an offhand bench grinder, what is the largest gap allowed between the work rest and the wheel?

    Show the answer

    A. 1/8 inch. 29 CFR 1910.215(a)(4) requires work rests on offhand grinders to be kept adjusted closely to the wheel with a maximum opening of 1/8 inch, so the work cannot jam between wheel and rest and break the wheel. The rest is clamped after each adjustment and never adjusted while the wheel is turning.

    From 29 CFR 1910.215(a)(4)

  4. 38. On a bench grinder where the operator stands in front of the guard opening, what is the most distance allowed between the wheel and the adjustable tongue at the top of the guard?

    Show the answer

    B. 1/4 inch. 29 CFR 1910.215(b)(9) requires the guard's peripheral member to adjust to the wheel's shrinking diameter, and the distance between the wheel periphery and the adjustable tongue (or the end of the peripheral member) at the top must never exceed 1/4 inch.

    From 29 CFR 1910.215(b)(9)

0 of 38 answered

Questions

Are these the real OSHA 10 General Industry exam questions?

No. The bodies that give the real exam keep its questions to themselves. Each question here is written for the rules or skills the exam tests, and its explanation shows the working or names the section of the regulation or code it comes from, so you learn the rule rather than one answer.

Is the practice test free?

Yes. All 38 questions and their explanations are free, with no sign-up. Your answers stay in your browser.

Checked against the rules in force on 2026-11-26. Rules and exam formats change: check the current rule and your exam provider's own information before the exam.