Free practice test
Practice for the journeyman electrician licence exam: NEC rules, calculations and theory. Pick an answer to see whether it is right and why, with the code section behind it.
In most states, or in the city where you work, a journeyman license is what lets you wire on your own, and the license exam is how you get it.
Pick an answer to see whether it is right. Each explanation shows why, with the rule or the working behind it, so a wrong answer still teaches you something.
NEC rules (20) · Calculations (15) · Theory and safety (10)
NEC requirements an electrician applies on the job: GFCI and AFCI, overcurrent protection, working space, receptacles, grounding electrodes, ampacity and wiring methods.
1. Table 310.16 lists 10 AWG THHN copper at 40 A in the 90 degree C column. Unless a specific exception for motors, air conditioning or similar loads applies, what is the largest overcurrent device that may protect it?
D. 30 A. The small-conductor rule caps overcurrent protection at 15 A for 14 AWG copper, 20 A for 12 AWG copper and 30 A for 10 AWG copper, whatever the ampacity table shows. 25 A is the cap for 10 AWG aluminum.
From NEC 240.4(D), small conductors, EC&M, Conductor Sizing (Part 1 of 2)
2. A feeder of 2 AWG THWN copper has an ampacity of 115 A, and no standard 115 A breaker exists. The conductors do not supply receptacles for cord-and-plug-connected portable loads. What is the largest breaker permitted?
A. 125 A. Where the ampacity does not match a standard rating, the next higher standard rating (here 125 A) is permitted, as long as the next size does not exceed 800 A and the conductors are not part of a branch circuit supplying more than one receptacle for cord-and-plug-connected portable loads.
From NEC 240.4(B) and Table 240.6(A), EEPower, National Electrical Code Basics: Sizing and Protecting Branch Circuit Conductors (Example 10)
3. Under the 2023 NEC, how many 20-ampere small-appliance branch circuits are required, at minimum, for the receptacles in a dwelling unit kitchen, dining room, pantry and similar areas?
B. Two. At least two 20-ampere, 120-volt small-appliance branch circuits must supply these receptacles, and the countertop receptacles must be served by at least two of them. They may not supply lighting or outlets in other rooms.
From NEC 210.11(C)(1) and 210.52(B) (2023), EC&M, NEC Requirements for Branch Circuits
4. Under the 2023 NEC, the required 20-ampere branch circuit for dwelling bathroom receptacles may also supply other outlets, such as the light and exhaust fan, only when:
A. It supplies a single bathroom and the other outlets are in that same bathroom. The bathroom receptacle circuit normally may serve no other outlets. The exception lets one 20-ampere circuit supply all the outlets in a single bathroom, as long as it serves only that bathroom.
From NEC 210.11(C)(3) and Exception (2023), EC&M, NEC Requirements for Branch Circuits
5. Under the 2023 NEC, AFCI protection is required for 120-volt, 15- and 20-ampere branch circuits supplying outlets in each of these dwelling areas EXCEPT:
C. Bathrooms. The dwelling AFCI list (moved to 210.12(B) in the 2023 edition) covers kitchens, laundry areas, family rooms, dining rooms, living rooms, parlors, libraries, dens, bedrooms, sunrooms, recreation rooms, closets, hallways and similar areas. Dwelling bathrooms are not on it; they need GFCI protection instead.
From NEC 210.12(B) (2023), City of Saint Paul DSI, AFCI Protection Requirements
6. In a dwelling family room with a wet bar, a 125-volt, 20-ampere receptacle is installed 4 feet from the bar sink. GFCI protection for that receptacle is:
A. Required, because it is within 6 feet of the sink. Dwelling receptacles within 6 feet of a sink need GFCI protection wherever the sink is. The rule covers any dwelling sink, such as a wet bar or utility sink, not only kitchen and bathroom sinks.
From NEC 210.8(A), dwelling units, areas within 6 ft of sinks, Schneider Electric, Residential GFCI protection: An NEC guide for electricians
7. Under the NEC, receptacles along the walls of a dwelling living room must be placed so that no point along the floor line of any wall space is more than how far, measured horizontally, from a receptacle?
B. 6 ft. No point along the floor line may be more than 6 feet from a receptacle, the length of a typical appliance cord. That is why receptacles can be up to 12 feet apart along a wall but no more than 6 feet from a door or wall end.
From NEC 210.52(A)(1), EC&M, Receptacles in Dwellings
8. Under the NEC, receptacles serving a dwelling kitchen wall countertop must be placed so that no point along the countertop wall line is more than how far from a receptacle outlet?
D. 24 in. Each countertop wall space 12 inches or wider needs a receptacle, and no point along the wall line may be more than 24 inches (2 feet) from one. A sink, range or refrigerator breaks the countertop into separate spaces.
From NEC 210.52(C)(1), EC&M, Receptacles in Dwellings
9. Under the NEC, a one-family dwelling needs at least one outdoor receptacle at the front and one at the back, readily accessible from grade and not more than how high above grade?
D. 6 1/2 ft. For one- and two-family dwellings, a GFCI-protected receptacle readily accessible from grade and no more than 6 1/2 feet above grade is required at the front and at the back of each unit.
From NEC 210.52(E)(1), EC&M, Receptacles in Dwellings
10. Under the 2023 NEC, receptacles may not be installed within a zone measured how far horizontally and vertically from the top of a bathtub rim or shower stall threshold?
C. 3 ft horizontally and 8 ft vertically. The no-receptacle zone extends 3 feet horizontally and 8 feet vertically from the tub rim or shower threshold, including the space directly above the tub or shower. The 2023 edition also prohibits receptacles inside the tub or shower itself.
From NEC 406.9(C) (2023), EC&M, NEC Requirements for Receptacles
11. Under the 2023 NEC, a panelboard 20 inches wide needs a working space in front of it at least how wide?
D. 30 in. Working space must be at least 30 inches wide, or the width of the equipment if that is greater. It may be centered on the equipment or offset, and it must let equipment doors open at least 90 degrees.
From NEC 110.26(A)(2) (2023), EC&M, NEC Requirements for Working Clearances
12. A 480Y/277-volt panelboard with exposed live parts when open faces a concrete block wall across the aisle. What is the minimum depth of working space in front of it?
A. 3 1/2 ft. Concrete, brick and tile walls count as grounded, so this is Condition 2. For 151 to 600 volts to ground (277 V here), Condition 2 needs 3 1/2 feet; Condition 1 would need 3 feet and Condition 3 would need 4 feet.
From NEC Table 110.26(A)(1), Condition 2, IAEI Magazine, Working Space Requirements for Electrical Panelboards
13. Under the 2023 NEC, a single ground rod must be supplemented by an additional electrode unless the rod alone has a measured resistance to earth of:
D. 25 ohms or less. A single rod, pipe or plate electrode needs a supplemental electrode unless it measures 25 ohms or less. Once the supplemental electrode is added, the NEC does not require any particular resistance.
From NEC 250.53(A)(2) (2023), EEPower, National Electrical Code 2023 Basics: Grounding and Bonding Part 12
14. Under the 2023 NEC, a service has 3/0 AWG copper service-entrance conductors. What size copper grounding electrode conductor is required to the metal underground water pipe electrode?
B. 4 AWG. The grounding electrode conductor is sized from Table 250.66 by the largest service-entrance conductor: 2/0 or 3/0 copper calls for a 4 AWG copper grounding electrode conductor. A conductor that runs only to a rod may be 6 AWG, and one that runs only to a concrete-encased electrode may be 4 AWG.
From NEC Table 250.66 (2023), EEPower, National Electrical Code 2023 Basics: Grounding and Bonding Part 12
15. One raceway holds two 120/240-volt, 3-wire single-phase circuits (two hots and a neutral each, supplying linear loads) plus one equipment grounding conductor. How many current-carrying conductors are counted for ampacity adjustment?
A. 4. The neutral of a 3-wire, single-phase 120/240-volt circuit carries only the unbalanced current and is not counted, and equipment grounding conductors are never counted. That leaves the four ungrounded conductors, so the 80% factor for four to six conductors applies.
From NEC 310.15(E)(1) and 310.15(F) (2023), EC&M, NEC Requirements for Conductors
16. Under the 2023 NEC, conductors installed in a raceway must be stranded (unless specifically permitted to be solid) when they are:
B. 8 AWG and larger. Conductors 8 AWG and larger in a raceway must be stranded, unless the Code specifically permits or requires solid. Solid 10, 12 and 14 AWG may be pulled in raceways.
From NEC 310.3(C) (2023), EC&M, NEC Requirements for Conductors
17. Under the 2023 NEC, flexible metal conduit may serve as the equipment grounding conductor only where its total length in the same ground-fault return path is not more than:
D. 6 ft. Flexible metal conduit counts as an equipment grounding conductor only for a combined length of 6 feet or less (with its other conditions met). Longer runs need a wire-type equipment grounding conductor or bonding jumper.
From NEC 250.118, flexible metal conduit (2023), EEPower, National Electrical Code 2023 Basics: Grounding and Bonding Part 1
18. Under the 2023 NEC, an insulated equipment grounding conductor 6 AWG or smaller must have a continuous outer finish that is:
A. Green, or green with one or more yellow stripes. Insulated equipment grounding conductors 6 AWG and smaller must be green or green with yellow stripes along their whole length. Only 4 AWG and larger may be reidentified with green marking at accessible points.
From NEC 250.119(A) and (B) (2023), EC&M, NEC Requirements for Branch Circuits
19. Under the 2023 NEC, Type NM cable must be supported and secured at intervals not exceeding:
B. 4 1/2 ft. NM cable must be supported and secured at intervals of no more than 4 1/2 feet. Resting the cable on trusses supports it but does not secure it, so staples or other listed fasteners are still needed.
From NEC 334.30 (2023), EC&M, Code Quiz: Uses Permitted for NM Cable
20. Under the NEC, EMT must generally be securely fastened within what distance of each box or termination, and at what maximum interval?
C. 3 ft of each box, and every 10 ft. EMT is fastened within 3 feet of each box, cabinet or termination and at intervals of no more than 10 feet. The 5-foot distance is only an exception for unbroken lengths where framing does not allow fastening within 3 feet.
From NEC 358.30(A) and (B), EC&M, Stumped by the Code? Rules for Securing and Supporting Raceways
Ohm's law, power, voltage drop, box fill, dwelling load, ampacity adjustment and conduit fill worked the way the exam asks them.
21. A 20-ohm resistive load is connected to 240 volts. What current does it draw?
B. 12 A. Ohm's law: I = V / R = 240 V / 20 ohms = 12 A.
From Ohm's law, V = IR (OpenStax College Physics, 21.1 Resistors in Series and Parallel)
22. Resistors of 10, 20 and 30 ohms are connected in series across 120 volts. What is the circuit current?
A. 2 A. Series resistances add: 10 + 20 + 30 = 60 ohms. Then I = 120 V / 60 ohms = 2 A, and that same current flows through each resistor.
From Resistors in series, total resistance is the sum (OpenStax College Physics, 21.1 Resistors in Series and Parallel)
23. Two 12-ohm heating elements are connected in parallel. What is their combined resistance?
D. 6 ohms. For parallel resistors, 1/R = 1/12 + 1/12 = 2/12, so R = 6 ohms. Two equal resistors in parallel always give half of one, and the total is always less than the smallest branch.
From Resistors in parallel, reciprocal rule (OpenStax College Physics, 21.1 Resistors in Series and Parallel)
24. A 1,800-watt portable heater runs on 120 volts. How much current does it draw?
C. 15 A. Power equals current times voltage (P = I x V), so I = P / V = 1,800 W / 120 V = 15 A.
From Joule's law, P = IV (OpenStax College Physics, 21.1 Resistors in Series and Parallel)
25. A current of 10 amperes flows through a 5-ohm resistor. How much power does the resistor dissipate?
C. 500 W. P = I squared x R = 10 x 10 x 5 = 500 W. The answer 50 W comes from multiplying current by resistance, which gives volts, not watts.
From Power in a resistor, P = I squared R (OpenStax College Physics, 21.1 Resistors in Series and Parallel)
26. Under the 2023 NEC, a branch circuit supplies a 24-ampere continuous load and nothing else. What is the smallest overcurrent device rating permitted (without a 100% rated assembly)?
C. 30 A. The overcurrent device must be rated at least 125% of the continuous load plus 100% of the noncontinuous load: 24 A x 1.25 = 30 A. A 30 A device is the minimum.
From NEC 210.20(A) (2023), EC&M, NEC Requirements for Branch Circuits
27. Six current-carrying 1 AWG THHN copper conductors share one raceway at a normal 30 degree C ambient. Table 310.16 lists 145 A for 1 AWG in the 90 degree C column. What is the adjusted ampacity?
C. 116 A. Four to six current-carrying conductors take an 80% adjustment factor from Table 310.15(C)(1), applied to the 90 degree C ampacity: 145 A x 0.80 = 116 A. The 70% factor (101.5 A) is for seven to nine conductors.
From NEC Table 310.16 and Table 310.15(C)(1), EEPower, National Electrical Code Basics: Sizing and Protecting Branch Circuit Conductors (Example 5)
28. Six current-carrying 1 AWG THHN copper conductors (145 A in the 90 degree C column) run in one raceway where the ambient temperature is 38 degrees C. The correction factor for 36 to 40 degrees C in the 90 degree C column is 0.91. What is the resulting ampacity?
A. 105.6 A. Apply both factors to the 90 degree C ampacity: 145 A x 0.80 (four to six conductors) x 0.91 (ambient) = 105.6 A. Using only one of the two factors gives 116 A or 132 A.
From NEC 310.15(B) and 310.15(C)(1), EEPower, National Electrical Code Basics: Sizing and Protecting Branch Circuit Conductors (Example 6)
29. A metal box with internal cable clamps has two 12/2 with ground NM cables entering it and one receptacle installed. What is the minimum box volume required?
C. 18 cubic inches. Count: 4 insulated conductors, 1 for all the clamps, 2 for the receptacle yoke, 1 for all the equipment grounding conductors = 8 conductor volumes. Each 12 AWG volume is 2.25 cubic inches, so 8 x 2.25 = 18 cubic inches.
From NEC 314.16(B)(1) through (B)(5) and Table 314.16(B), EC&M, NEC Requirements for Sizing Outlet Boxes
30. A single-gang nonmetallic box with no internal clamps contains two 14/2 with ground NM cables and one single-pole switch. What box fill volume do these take up?
B. 14 cubic inches. Count: 4 insulated conductors, 2 for the switch yoke, 1 for both equipment grounding conductors, and nothing for clamps because there are none = 7 volumes. At 2.00 cubic inches per 14 AWG volume, 7 x 2.00 = 14 cubic inches.
From NEC 314.16(B)(1) through (B)(5) and Table 314.16(B), EC&M, NEC Requirements for Sizing Outlet Boxes
31. Under the 2023 NEC, what is the general lighting and general-use receptacle load for a 2,400-square-foot dwelling, before demand factors?
B. 7,200 VA. The 2023 NEC sets a minimum unit load of 3 VA per square foot for dwellings (220.41): 2,400 x 3 = 7,200 VA.
From NEC 220.41 (2023), EC&M, Changes to Dwelling Unit Calculations in the 2026 NEC
32. Under the 2023 NEC, a 2,000-square-foot dwelling has the two required small-appliance circuits and one laundry circuit. What is the total of these loads plus general lighting, before demand factors?
D. 10,500 VA. General lighting is 2,000 x 3 VA = 6,000 VA. Each small-appliance and laundry circuit is counted at 1,500 VA: 3 x 1,500 = 4,500 VA. Total 6,000 + 4,500 = 10,500 VA.
From NEC 220.41 and 220.52(A) and (B), EC&M, Dwelling Unit Calculations
33. A 120-volt, single-phase circuit carries 16 amperes to a load 100 feet away (one way) on 12 AWG copper (6,530 circular mils). Using K = 12.9 for copper, what is the voltage drop?
B. 6.3 V. VD = 2 x K x I x L / CM = 2 x 12.9 x 16 x 100 / 6,530 = 6.3 V. The 2 accounts for both the outgoing and return conductors; leaving it out gives 3.2 V.
From Voltage drop formula and Chapter 9 Table 8 circular mils, EEPower, National Electrical Code Basics: Computing Voltage Drop in Branch Circuits and Feeders Part 2
34. A three-phase, 208-volt load draws 60 amperes over 6 AWG copper (26,240 circular mils) run 150 feet one way. Using K = 12.9, what is the voltage drop?
D. 7.7 V. For three-phase, VD = 1.732 x K x I x D / CM = 1.732 x 12.9 x 60 x 150 / 26,240 = 7.7 V. Using the single-phase multiplier of 2 instead of 1.732 gives the wrong answer of 8.8 V.
From Voltage drop formulas (single-phase and three-phase), EC&M, Code Calculations
35. A raceway will hold three 500 kcmil THHN (0.7073 square inch each), one 250 kcmil THHN (0.3970 square inch) and one 3 AWG THHN (0.0973 square inch). What is the smallest total internal area the raceway can have?
C. 6.54 square inches. The conductors total 2.6162 square inches. With more than two conductors the fill limit is 40% (Chapter 9, Table 1), so the raceway needs at least 2.6162 / 0.40 = 6.54 square inches. 53% applies to one conductor and 31% to two.
From NEC Chapter 9, Table 1 and Table 5, EC&M, Code Q&A: Sizing a Raceway
Electrical theory, grounding versus bonding, GFCI basics and OSHA lockout and deenergizing rules.
36. Under OSHA's lockout/tagout standard, who normally removes a lockout device from an energy-isolating device when the work is done?
C. The employee who applied it. OSHA requires each lock or tag to be removed by the employee who put it on. The only exception is a documented employer procedure used when that employee is not at the facility, including efforts to reach them before they resume work.
From 29 CFR 1910.147(e)(3)
37. A machine has been shut down, its disconnect locked out, and its stored energy released. Under OSHA 1910.147(d), what must the authorized employee do before starting work?
A. Verify that the machine is actually isolated and deenergized. The last step of the lockout sequence is verification: before work starts, the authorized employee confirms that isolation and deenergization were actually achieved. A lock on a handle does not prove the equipment is dead.
From 29 CFR 1910.147(d)(6)
38. Under OSHA 1910.333, a qualified person tests a circuit rated over 600 volts nominal to confirm it is deenergized. When must the test instrument be checked for proper operation?
B. Immediately before and immediately after the test. For circuits over 600 volts nominal, OSHA requires the tester to be proved immediately before and immediately after the test, so a dead reading cannot come from a failed meter.
From 29 CFR 1910.333(b)(2)(iv)(B)
39. Under OSHA 1910.333, which of these may NOT be used as the only means of deenergizing a circuit before employees work on it?
D. A control circuit push button or selector switch. Control circuit devices such as push buttons, selector switches and interlocks may not be the sole means of deenergizing equipment. The circuit must be disconnected from every energy source with a true disconnecting device.
From 29 CFR 1910.333(b)(2)(ii)(B)
40. A Class A GFCI opens the circuit when the current leaking to ground reaches about:
A. 4 to 6 milliamperes. A GFCI compares the current going out with the current coming back and trips when the difference, the fault current to ground, exceeds a range of about 4 to 6 mA. That is low enough to protect a person, which is why it is called personnel protection.
From Office of Congressional Workplace Rights, Fast Facts: Ground-Fault Circuit Interrupters
41. On a construction site where the employer protects workers with GFCIs (rather than an assured equipment grounding conductor program), which receptacle outlets in use by employees must have GFCI protection under OSHA?
C. All 120-volt, single-phase, 15- and 20-ampere receptacles that are not part of the building's permanent wiring. OSHA's construction rule requires approved GFCIs on all 120-volt, single-phase, 15- and 20-ampere receptacle outlets in use by employees that are not part of the permanent wiring. The employer may instead run an assured equipment grounding conductor program.
From 29 CFR 1926.404(b)(1)(i) and (b)(1)(ii)
42. Under the 2023 NEC, why can the earth not serve as the effective ground-fault current path?
D. Its resistance is too high to let enough fault current flow to open the overcurrent device. The effective ground-fault current path must be a low-impedance circuit that carries enough fault current back to the source to trip the breaker or blow the fuse. The earth's resistance is far too high, so a fault returning only through the earth can leave metal parts energized.
From NEC 250.4(A)(5) (2023), as explained in EEPower, National Electrical Code 2023 Basics: Grounding and Bonding Part 1
43. Under the 2023 NEC, in a building supplied by a service, where is the grounded (neutral) conductor connected to the equipment grounding conductors and the service enclosure?
A. At the service disconnecting means, through the main bonding jumper. The neutral-to-ground connection is made at the service by the main bonding jumper. On the load side of the service disconnect the grounded conductor may not be connected to ground or to equipment grounding conductors again, except where Article 250 specifically permits it.
From NEC 250.24(B) and (C) (2023), as explained in EEPower, National Electrical Code 2023 Basics: Grounding and Bonding Part 3
44. Connecting metal parts with a reliable conductor so they are at the same potential and form a continuous path for fault current is called:
C. Bonding. Bonding joins metal parts so they have electrical continuity and equal potential, which keeps a person from touching two surfaces at different voltages. Grounding is the connection to the earth or to a conductive body that serves as ground.
From NEC Article 100 definitions of Bonding and Grounding, as explained in EEPower, National Electrical Code 2023 Basics: Grounding and Bonding Part 1
45. Three resistors of different values are connected in series across a 120-volt source. How does the current compare through each resistor?
B. It is the same through every resistor. A series circuit has only one path, so the same current flows through every resistor. What differs is the voltage drop across each one, which is the current times that resistor's value.
From OpenStax College Physics, 21.1 Resistors in Series and Parallel
Offered to people preparing for the journeyman electrician exam. We may earn a share of what you pay if you buy through these links. It never changes your price, and the sellers have no say in the jobs we list. As an Amazon Associate I earn from qualifying purchases.
More free practice tests: EPA 608 Practice Test · Journeyman Plumber Practice Test · OSHA 10 Practice Test · OSHA 30 Practice Test · Electrical Aptitude Test Practice · UA Plumbers and Pipefitters Aptitude Test Practice · EEI CAST Test Practice · Contractor Business and Law Practice Test · CSLB Law and Business Practice Test · Florida Business and Finance Exam Practice Test · Arizona Statutes and Rules Exam Practice Test · Nevada Business and Law Exam Practice Test · Utah Business and Law Exam Practice Test · Louisiana Business and Law Exam Practice Test · South Carolina Business and Law Exam Practice Test · North Carolina General Contractor Exam Practice Test · Oregon CCB Test Practice Test · New Mexico Business and Law Exam Practice Test · Alabama Business and Law Exam Practice Test · Hawaii Business and Law Exam Practice Test · OSHA 10 General Industry Practice Test · Forklift Practice Test
No. The bodies that give the real exam keep its questions to themselves. Each question here is written for the rules or skills the exam tests, and its explanation shows the working or names the section of the regulation or code it comes from, so you learn the rule rather than one answer.
Yes. All 45 questions and their explanations are free, with no sign-up. Your answers stay in your browser.
Checked against the rules in force on 2026-11-26. Rules and exam formats change: check the current rule and your exam provider's own information before the exam.